The LV series are solid porcelain open type bushings designed in accordance with the standard DIN 42539/42530 .<br> Primarily used for indoor and outdoor applications in the field of distribution transformers, these bushings are available in several designs and can be customized to fit almost any kind of customer requirement upon request (i.e. tin plating, special drillings, special connectors, etc.). The LV series features a porcelain insulating body on the oil side; in addition, rods are available both in copper or brass.


Keywords



Product description


ARES bushings  1kV bushing series according to DIN42530 and EN50386 with a rated current from 250A to 5000A, fully interchangeable with DIN standard for easy replacement. Can be Shipped pre-assembled  or fully assembled, special designs can be  provided  for external environmental conditions, ensuring a longer service life and reducing leakage issues we can supply different gaskets such as NBR, VITON, FVMW -60 or CORK.

DIN standard bushing outline dimensions (1~3kV/250~630A)

 

Sequence NumberCodeModelDimensionsOpeningArcing distanceCreep distanceShieldWeight
(kg)
Hh2h3Mdd1d2d3d0h1
1AM.DAA.001DIN-1/25020562.528.5M12×1.755060502849551 single umbrella1
2AM.DAD.001DIN-1/6302607843M20×2.57085704559701 single umbrella2.4
3AM.DBA.001DIN-3/25027287.528.5M12×1.7575706039891201 single umbrella1.5
4AM.DBD.001DIN-3/63031810343M20×2.591857045891201 single umbrella2.9
As a standard product we can offer both historical DIN standard bushings and the latest EN range of bushings, these product cover the requirements of distribution and power transformer manufacturers. We can offer ratings from 1kV through to 52kV and up to 12500A with a wide variety of creepage distances to meet all environemental conditions.
 
All outdoor bushings are manufactured and tested in accordance with IEC60137, the detail of the bushing is governed by either historical DIN specification (no longer live standards but still utilsed widely by the transformer and distribution industry) or the latest range of EN specifications (EN50386 & EN50180).
 
Air end termination is typically either the screwed conductor stem or flag terminal (various hole arrangements are available) and the oil end termination can be as the air end termination or a machined hole arrnagement to suit the customers requirements.For the metal parts surface finishing, we can make as per customer requirements such as tin plating, galvanising, cooper plating.
 As a standard product we can offer both historical DIN standard bushings and the latest EN range of bushings, these product cover the requirements of distribution and power transformer manufacturers. We can offer ratings from 1kV through to 52kV and up to 12500A with a wide variety of creepage distances to meet all environemental conditions.
 
All outdoor bushings are manufactured and tested in accordance with IEC60137, the detail of the bushing is governed by either historical DIN specification (no longer live standards but still utilsed widely by the transformer and distribution industry) or the latest range of EN specifications (EN50386 & EN50180).
 
Air end termination is typically either the screwed conductor stem or flag terminal (various hole arrangements are available) and the oil end termination can be as the air end termination or a machined hole arrnagement to suit the customers requirements.For the metal parts surface finishing, we can make as per customer requirements such as tin plating, galvanising, cooper plating.
 

 

Note: Other specifications can be customized according to customer needs.