Product Center

+
  • 123.jpg
  • 1111.jpg

Epoxy Bushing BFG-1.2kV/1000~5000A Red Color

Low Voltage Bushings Up to 5kV Class Low voltage bushings are essential components for ensuring reliable electrical connections on the low voltage side in power systems and liquid-filled transformers up to 5 kV. Designed to meet the unique demands of low voltage applications, bushings provide superior insulation and mechanical support, enabling efficient power transmission while maintaining safety and system integrity. Engineered to withstand mechanical stress and manufactured with durable materials, our low voltage bushings are rigorously tested to meet industry standards and provide optimal performance and reliability.


Keywords



Product description


Rated voltage:2.5kV

Rated current:5200A

Power frequency withstandvoltage:12kV/1min

Lightning impulse:45kV

Cantilever tolerance:3150N

Creepage distance:≥61mm

Epoxy Bushing

Epoxy bushings are indispensable key components on the low-voltage side of transformers. They utilize the epoxy resin's excellent comprehensive properties (electrical, mechanical, sealing, and weather resistance) to provide a safe and reliable pathway for low-voltage, high-current conductors, offering insulation, support, sealing, and connection. Their characteristics of stable performance, maintenance-free operation (compared to older oil-impregnated paper bushings), and flexible design make them an extremely common and successful standard solution for the low-voltage side of modern transformers, especially dry-type and distribution transformers.

1.High Performance

Working temperature range from -40~130℃;

Excellent injection equipment to ensure no pores inside the insulation body;

Special surface treatment to ensure the bushing should not leak in long term service;

2.Rigous Test

Dielectric Tests

Basic Impulse level test: for 1.2kV class the impulse voltage is 30kV (full wave), and for 2.5kV class, the impulse voltage is 45kV (full wave);

High voltage 50Hz & 60Hz withstand test: for 1.2kV class, test voltage is 10kV/1min., for 2.5kV class, the test voltage is 2.0 kV/ 1min.

Mechanical Strengthen Tests

Leakage test;     Stud push-out test;    Stud torque strength test;    Cantilever test;     Flange torque test

Environmental test

It includes thermal cycle test.  The tested temperature range is -40~130℃, withstand 20 cycles

Dry type Resin bushing outline dimensions ( 3kV/1000~5000A plate connected bushing )

Note: Other specifications can be customized according to customer needs.

Related download

Message

We can recommend suitable products for you according to your needs, please fill in the form below, we will contact you in time!


Submit